- Draw your floor area onto squared paper, marking any unheated areas such as a bath, sink, toilet or kitchen island unit.
- Calculate the area to be heated by subtracting any unheated areas from the total floor area.
- Choose the kit size that is the closest match for your heated floor area. If the area to be heated falls between two ElectroMat® kit sizes, always choose the smaller kit size to avoid the risk of overheating, and add additional decoupling membrane to cover the unheated areas if necessary.
![]()
Example heated area calculation
Small en-suite shower room 2x2m²
4m² de-coupled floor area.
1.7m² heated floor area.
Thermostat positioned outside the room.
In this instance, the area to be heated by the ElectroMat® underfloor heating kit is 1.7m², with the remaining 2.3m² floor area to be left unheated.
Choosing the 1.5m² kit ensures sufficient cable to heat the 1.7m² space, laying the cable at the recommended 3 dimple spacing. The 1.5m² kit includes 2m² of decoupling membrane – an additional 2m² of decoupling membrane can be purchased to run underneath the shower, basin and WC, if desired.
| ElectroMat® kit size (m²) | Maximum area covered by supplied de-coupling membrane (m²) | Max recommended heating area (m²) |
|---|---|---|
| 1 | 2 | 1.2 |
| 1.5 | 2 | 1.7 |
| 2 | 3 | 2.3 |
| 2.5 | 3 | 3.0 |
| 3 | 4 | 3.5 |
| 4.5 | 5 | 4.7 |
| 5.5 | 6 | 5.8 |
| 6.5 | 7 | 7.0 |
| 9 | 10 | 9.5 |
| 11.5 | 12 | 11.8 |
| 13.5 | 14 | 14 |
| 18 | 19 | 19.0 |